| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet can cause the RSLinx® Classic service to crash due to insufficient data length validation, requiring a restart of the service to recover. |
| A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet targeting the Forward Close service can cause the RSLinx® Classic service to crash, requiring a restart of the service to recover. |
| A denial-of-service security issue exists within RSLinx® Classic. The security issue stems from improper handling of a malformed packet. A crafted CIP packet can cause the RSLinx® Classic service to crash, requiring a restart of the service to recover |
| A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet with an oversized embedded message request can cause the RSLinx® Classic service to crash, requiring a restart of the service to recover. |
| Stack-based buffer overflow in OPCTest.exe in Rockwell Automation RSLinx Classic before 3.73.00 allows remote attackers to execute arbitrary code via a crafted CSV file. |
| Buffer overflow in RSEds.dll in RSHWare.exe in the EDS Hardware Installation Tool 1.0.5.1 and earlier in Rockwell Automation RSLinx Classic before 2.58 allows user-assisted remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a malformed .eds file. |
| LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage) via a zero-byte UDP packet that is not properly handled by Logger.dll. |
| Buffer overflow in LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via a UDP packet with a certain integer length value that is (1) too large or (2) too small, leading to improper handling by Logger.dll. |
| A denial-of-service vulnerability exists in the Ethernet/IP server functionality of Rockwell Automation RSLinx Classic 2.57.00.14 CPR 9 SR 3. A specially crafted network request can lead to a denial of service. An attacker can send a sequence of malicious packets to trigger this vulnerability. |
| Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions. |
| Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions. |
| FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition. |
| FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to use specially crafted requests to traverse the file system and expose sensitive data on the local hard drive. |
| FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. The parsing mechanism that processes certain file types does not provide input sanitation. This may allow an attacker to use specially crafted files to traverse the file system and modify or expose sensitive data or execute arbitrary code. |
| FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data. |
| In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic. |
| A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an attacker to exploit a stack-based buffer overflow condition. |
| Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote threat actor to intentionally send a malformed CIP packet to Port 44818, causing the software application to stop responding and crash. This vulnerability also has the potential to exploit a buffer overflow condition, which may allow the threat actor to remotely execute arbitrary code. |
| Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. A remote, unauthenticated threat actor may intentionally send specially crafted Ethernet/IP packets to Port 44818, causing the software application to stop responding and crash. The user must restart the software to regain functionality. |
| Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote, unauthenticated threat actor to intentionally send a malformed CIP packet to Port 44818, causing the RSLinx Classic application to terminate. The user will need to manually restart the software to regain functionality. |